Industry Leaders in AC / DC Solutions

Ensure uninterrupted power supply round the clock using La Marche's durable
Battery Chargers, UPS, and Power Conversion Solutions. Keep your vital
systems operational and seamlessly running under any circumstances.

SGC SCR Charger

SGC SCR Charger

Smart Microprocessor Controlled SCR

Output:
24 / 48 / 125 VDC

Input:
Single-Phase: 120 / 208 / 240 VAC
Frequency: 60Hz ±3Hz

Applications:
Utility
Switchgear
Process Control
Oil Exploration

  

The La Marche SGC Model is designed specifically to provide an economical and robust solution for Auxiliary DC Control Power Systems in Substations. This Smart Microprocessor controlled Battery Charger is designed with PWM controls to provide the highest reliability that is required for maintaining and recharging the batteries, along with supporting the continuous loads in the auxiliary DC system.

The La Marche SGC is designed per NEMA PE5, C62.41A and UL safety requirements. This Filtered Battery Charger meets NEMA PE5 filtering requirements and has 0.5% DC voltage regulation from no load to full load (over the specified input voltage, frequency and ambient temperature ranges). Those features along with its Temperature Compensation capability make this model suitable for various types of batteries such as flooded lead acid, VRLA and NiCad. SGC is equipped with a two-line LCD display which shows output voltage and current, along with an alarm status text description. Individual LED indicators provide local supervision and Form “C” Alarm Contacts provide remote annunciation. Communication Protocols are also available.

Standard Features

  • Smart Microprocessor Controlled SCR Technology
  • Filtered Battery Charger
  • Automatic AC Voltage Compensation
  • AC & DC Surge Protection (MOV)
  • AC & DC Breaker
  • Temperature Compensation
  • Float/Equalize Mode Switch
  • Digital Float and Equalize Adjustments
  • Digital Current Limit Adjustment 50 to 110%
  • ±0.5% DC Voltage Regulation
  • Over Temperature Protection
  • Battery Continuity Test
  • Alarm LED’s and Form “C” Contacts
  • LCD Display
  • 0°C to +50°C Operating Temperature
  • Soft Start
  • Reverse Polarity Protection
  • Conformal Coated Circuit Boards
  • Meets NEMA PE5 and IEEE-2405
  • UL/CUL 1012 (Pending)
  • 2 Year Warranty
     
Datasheets
User Manuals
Enclosures
 
Breakers and Protection :
Breakers and Protection
Lightning Arrestor
11J
Level-2 Ripple Filter (Aka: Battery Eliminator)
11Y
External Temperature Compensation Probe 100ft
Communications :
Communications
DNP3.0
57L
MODBUS RTU (RS-485)
57Y
MODBUS (TCP/IP)
Miscellaneous :
Miscellaneous
---
ABD1 Multi-Tap 120/208/240V Input

Battery Charger Sizing Calculator
Result has been sent on provided address.
Please check inbox.
Options (check applicable boxes)
Or
Result has been sent. Please check your email
A = (1.15 X Ah / H) + L
  • A = DC output rating of charges
  • 1.15 = Efficiency factor to return 100% of amp hours removed from a lead acid battery.
  • 1.4 = Efficiency factor to return 100% of amp hours removed from a NiCad battery.
  • Ah = Battery amp hours (Removed)
  • H = Hour recharge time
  • L = Amp continuous load on system while recharging the battery