Circuit Breaker Distribution Panels - BPK Series

  

Circuit Breaker Distribution Panels are designed to provide protection for multiple load/distribution circuits. The circuit breakers fast trip response assures the Circuit Breaker Distribution Panel-BPK Series Data Sheet panel breaker will trip before the main circuit breaker/fuse so that the power will not be interrupted from other critical DC loads if an overload occurs. BPK Panels utilize UL recognized breakers with an interrupting capacity of 5,000 amps DC at 65 volts. Connection to the load is made directly to the load side terminal screw of the breaker. For breakers size up to 70 amps, the terminal is a 10-32 stud with a recommend maximum #6 AWG wire size. For 100 amp breakers, the terminal is a ¼ - 20 stud with a recommended maximum #4 AWG wire size. Base panel does not include circuit breakers. For information on available circuit breaker sizes, see list price sheet. A blank 1.75" high panel (1RU) is recommended below breaker panel for ease of installation.

BPK Data Sheet