ESCR II

ESCR II

SCR Charging Technology

Output :
24 VDC
30, 40 or 40 Amps

Input:
120/208-240 VAC

Applications:
Generators, Compressors and Engine Starting

  

The ESCR II engine starting battery charger product line utilizes microprocessor controlled SCR Charging Technology. The PWM control provides the highest reliability that is required for maintaining and recharging engine start batteries for generator sets. This charger is suitable for various types of batteries such as flooded lead acid, VRLA and NiCad. The 0.5% regulation, temperature compensation, battery check, equalize timer along with adjustable output voltage and current limiting assures longevity and performance for your batteries. This economical solution equipped with advanced features incorporates La Marche quality and reliability.

 • Microprocessor Controlled SCR Technology
 • AC Input: 120/208-240VAC (50Hz/60Hz)
 • DC Input: 24VDC
 • Automatic AC Input Voltage Compensation
 • AC & DC Breakers
 • Filtering Suitable for VRLA Batteries
 • Battery Fault Detection
 • Front Panel Equipped with LCD Display
 • 3 Year Warranty

AC INPUT120/208 - 240 VAC ±10%, 50/60HZ, Single Phase
DC OUTPUT30A @ 24V
40A @ 24V
50A @ 24V
REGULATIONLine: <±0.5%
Load: <±0.5%
OUTPUT FILTERING (W/ Battery Connected)< 500 mV RMS
InputBreaker with Surge Protection
OutputBreaker with Surge Protection
BATTERY CELL SELECTION24 Volts
12L
18NC
19NC
20NC
OUTPUT CURRENT LIMITFactory set at 105%
Adjustable from 50 - 105%
METERINGLCD DC Output Digital Voltmeter and Ammeter (1%)
Float Voltage2.12 - 2.3 volts/cell (Lead)
1.39 - 1.45 volts/cell (NiCad)
Equalize Voltage2.25 - 2.40 volts/cell (Lead)
1.45 - 1.6 volts/cell (NiCad)
Float and Equalize ButtonSwitch from Float to Equalize
Configure ButtonOutput Settings
Voltage and Cells
Adjust Voltage for Float & Equalize
Adjust Alarm Settings and Delay
Enable/Disable Temperature Compensation
Equalize Timer
~ Multi-Mode Equalize Timer and Light; adjustable from 1 - 144 hrs
~ Five selectable modes: Manual, 7-day, 14-day, 30-day and Equalize after Low DC Voltage and/or AC Failure (Default Factory Setting)
Reset ButtonRestarts the Unit
Lamp Test ButtonTests LCD Display & LED's
ALARM CONTACTSAC Failure
Low DC Voltage
High DC Voltage
Charger Failure
Form
LCD DisplayVolts
Amps
Status
LED IndicationsFloat (Green)
Equalize (Yellow)
AC ON (Green)
Charger Failure (Red)
Battery Fault (Red)
Current Limit (Red)
High DC Voltage (Red)
Low DC Voltage (Red)
Operating-20 to 50 C
Storage-40 to 85 C
Relative Humidity5% to 95% non-condensing
Controls11WExternal Temperature Probe 24ft
Miscellaneous09PConformal Coating PCB
Standards38HABS Certified Report (per unit, up to 3 units)
538IBC Certification Label
Enclosure Accessories080Drip Shield Kit