General Maintenance Procedure
Yearly 1. Blow out rectifier/inverter with a low-pressure air hose. 2. Make sure all connections are tight. 3. Perform a visual check on all internal components. 4. Check front panel meters and alarms for accuracy.
4th Year REPEAT ABOVE WITH THE ADDITION OF: 1. Check relay contacts for pitting or corrosion. 2. Check capacitors for leakage.
7th Year REPEAT ALL, WITH THE ADDITION OF: 1. Filter, resonating capacitors and control relays should be replaced.
10th Year REPEAT ALL WITH THE ADDITION OF: (except replacing capacitors and control relays, they should be replaced every 7 years) 1. Check magnetics, components and wiring for signs of excessive heat.
|
|
|
|
|
|
|
|
|